The MicroLogix 1400’s LCD, unlike the MicroLogix 1100’s, can be used to set the unit’s IP Address.
In today’s article we’ll show you the steps to do just that.
Setting the IP Address of a MicroLogix 1400 using the built-in LCD:
1) When the MicroLogix 1400 is powered on, it displays the I/O Status screen as shown below:
2) To set the Micro’s IP and MAC address using the LCD, we need to access it’s menu. To do this, press the ESC button and you should see the menu below:
3) Next, press the down arrow button four times to select “Advanced Set,” then press the OK button:
4) Here, press the down arrow button twice to select “ENET CFG,” then press the OK button:
5) Now press the down arrow button once to select IP Address and press the OK button.
6) To enter the Ethernet Setup you must provide the password t. However if the unit is new, or no password has been set, you can press the OK button to bypass this screen.
7) New MicroLogix 1400’s come setup to automatically obtain an IP Address using BOOT-P, as shown below:
8) To manually assign an IP Address, press the Down Arrow button twice to change the ENET Mode option to “static,” and then press the OK button.
NOTE: The display will not show a message stating that for this change to take effect the Micro will need to be power cycled. We will do this after entering our IP Address.
9) You can now use the Arrow buttons to change the IP Address to your desired value. When done, press the OK button.
10) Now use the Arrow buttons to change the Subnet Mask Address to your desired value. When done, press the OK button.
11) If you wish to enter a Gateway address, use the Arrow buttons to change the address to your desired value. When done, press the OK button.
12) If you wish to enter a Primary DNS address, use the Arrow buttons to change the address to your desired value. When done, press the OK button.
13) If you wish to enter a Secondary DNS address, use the Arrow buttons to change the address to your desired value. When done, press the OK button.
14) Now you’re finished setting up the MicroLogix 1400’s IP Address. As noted above, for the changes to take place you will need to cycle power to your Micro.
15) If you prefer to return to the I/O Status display, press the ESC button until you see the main menu, and then select “I/O Status” and press the OK button:
I hope the above procedure on how to set a MicroLogix 1400’s IP address using the LCD was helpful.
If you have any comments, questions, suggestions, or corrections, please feel free to leave them with us by filling out the “post a comment or question” link below.
Until next time, Peace ✌️
If you enjoy this episode please give it a Like, and consider Sharing as this is the best way for us to find new guests to come on the show.
Shawn M Tierney
Technology Enthusiast & Content Creator
Eliminate commercials and gain access to my weekly full length hands-on, news, and Q&A sessions by becoming a member at The Automation Blog or on YouTube. You'll also find all of my affordable PLC, HMI, and SCADA courses at TheAutomationSchool.com.
- Merry Christmas! - December 25, 2024
- 2024 Podcast Audience Polls: Vote before January 8th! - December 18, 2024
- All 2024 Audience Choice Polls: Vote before December 31st! - December 18, 2024
Discover more from The Automation Blog
Subscribe to get the latest posts sent to your email.
Buenas tardes quisiera saber si hay algun forma de recuperar el master password
saludos
Good afternoon Isaac,
I don’t speak Spanish, sorry,
Sincerely,
Shawn Tierney
Join my free community to follow along! You can also become a member and support our work at: Automation.Locals.com
Good afternoon. I wonder if there is any way to recover the master password greetings.
I have a feeling I know which Master Password he means . . .
Hey Rob,
I wondered if he tried just pressing enter as the default password is blank?
I’m not seeing any default passwords in the manual, and if I knew of a backdoor I wouldn’t post it as I know people who have been threatened with lawsuits if they supplied one 🙁
Sincerely,
Shawn Tierney
I am wondering if anyone else has had the problem of the ML1400 losing its IP address. It’s been set as Static, on two identical machines we have, and both have come up from a power cycle with a 0.0.0.0 address.
Good afternoon Rob,
Sounds familiar – I recommend checking to see if that was fixed in a firmware update…
Please let us know how you make out,
Shawn Tierney
Join my free community to follow along! You can also become a member and support our work at: Automation.Locals.com
The latest revison at RS is 15.07. Our controller is already at FW 15; I did not check for the minor rev, as I thought that something as drastic as losing its IP address would have been taken care of by rev. 2.0. The machines have been in production for a week, and we will be checking tomorrow whether they retained their IPs for this long.