In this week’s episode of The Automation Show, I cover how to use CCW to create and download a PanelView 800 program to read data from a CompactLogix, MicroLogix, and SLC-5/03 over a Data Highway 485 network:
For more information, check out the “Show Notes” located below the video.
The Automation Show, Episode 34 Show Notes:
Support our site and get early access to our videos, free downloads and more!
You can now support our site with a small monthly pledge and in turn receive instant rewards! To find out more visit https://automation.locals.com.
You can also purchase the entire season of The Automation Show for a one time donation of $25 at https://vimeo.com/ondemand/theautomationshow.
Thanks in advance for your support!
Vendors: Would you like your product featured on the Show, Podcast, and Blog? If you would, please contact me at: https://theautomationblog.com/contact
Until next time, Peace ✌️
If you enjoy this episode please give it a Like, and consider Sharing as this is the best way for us to find new guests to come on the show.
Shawn M Tierney
Technology Enthusiast & Content Creator
Eliminate commercials and gain access to my weekly full length hands-on, news, and Q&A sessions by becoming a member at The Automation Blog or on YouTube. You'll also find all of my affordable PLC, HMI, and SCADA courses at TheAutomationSchool.com.
- PRTG’s OPC UA Server: IT & OT Monitoring for your SCADA, HMI, or PLC (P226) - November 6, 2024
- 2024 Audience Choice Poll #10: Vote for your preferred Sensor / Reader Vendor - November 6, 2024
- Automation News for November 5, 2024 (N255) - November 5, 2024
Discover more from The Automation Blog
Subscribe to get the latest posts sent to your email.
What cable do you have going from the PV300 to the AIC+?
The PV800 uses a PM02 (unlike PVP) to go Seiral to Mini Din, but also has an RS485 TB:
https://literature.rockwellautomation.com/idc/groups/literature/documents/in/2711r-in001_-en-p.pdf
If you need more help then this, catch me at https://automation.locals.com
Shawn Tierney,
Instructor at http://www.TheAutomationSchool.com
Hi
I have an application where two micrologix 1200 and two panel view 300 and a rsview 32 connected via AIC+. Over DH485 NEtwork
I need to replace panel view 300 with 2711r-t4t. Plz advise how we can connect the same and which cables required
Dear Shawn,
we have an application deploying panel view micro 300 and compact logix L32 connected via serial DF1. Recently, we have to replace the panel view with panel view 800. we have successfully re-configure the panel view application to be suitable for panel view 800. the problem is that the panel view can not access the mapped integer data files in compact logix and gives alerts of no access or error in writing to tag , while it can access real tags. we followed steps given in below link
https://rockwellautomation.custhelp.com/app/answers/detail/a_id/55209/~/connecting-the-panelview-component%2F800-to-a-controllogix-or-compactlogix-using
Good morning Amr,
Sounds like you’re 90% there with the reals working but not the integers.
Can you check to see if the Integer array you mapped is a 16 bit INT, and not a 32 bit DINT?
PS – The process I used in this video for DH-485 would be nearly identical for DF1 and CompactLogix.
Hope this helps,
Shawn Tierney,
Instructor at http://www.TheAutomationSchool.com
Join my free community to follow along! You can also become a member and support our work at: Automation.Locals.com
Thanks Shawn for your kind support, I used DINT I will try SINT and let you know the result.
Thanks shown, I tried SINT not working. Then I tried INT and it works fine. I appreciate your help. Thanks.
You’re very welcome Amr, glad I was able to help,
Shawn Tierney,
Instructor at http://www.TheAutomationSchool.com
Join my free community to follow along! You can also become a member and support our work at: Automation.Locals.com