In this week's episode of The Automation Show, I cover how to use CCW to create and download a PanelView 800 program to read data from a CompactLogix, MicroLogix, and SLC-5/03 over a Data Highway 485 network:

For more information, check out the “Show Notes” located below the video.




The Automation Show, Episode 34 Show Notes:

Support our site and get early access to our videos, free downloads and more!

You can now support our site with a small monthly pledge and in turn receive instant rewards! To find out more visit https://Patreon.com/Automation.

You can also purchase the entire season of The Automation Show for a one time donation of $25 at https://vimeo.com/ondemand/theautomationshow.

Thanks in advanced for your support!

Vendors: Would you like your product featured on the Show, Podcast, and Blog? If you would, please contact me at: https://theautomationblog.com/contact

Sincerely,

Shawn Tierney
Automation Instructor and Blogger

Enjoy the benefits of membership! Insider news, rewards, & more: Patreon.com/automation
If you enjoyed my article, you may like my courses at TheAutomationSchool.com
Have a question on this topic? Click here to scroll down to the comment link
Have a news tip? Share it with us here

Avatar


Click HERE to scroll down to view or leave comments


5 Blog Comments

  1. Dear Shawn,
    we have an application deploying panel view micro 300 and compact logix L32 connected via serial DF1. Recently, we have to replace the panel view with panel view 800. we have successfully re-configure the panel view application to be suitable for panel view 800. the problem is that the panel view can not access the mapped integer data files in compact logix and gives alerts of no access or error in writing to tag , while it can access real tags. we followed steps given in below link
    https://rockwellautomation.custhelp.com/app/answers/detail/a_id/55209/~/connecting-the-panelview-component%2F800-to-a-controllogix-or-compactlogix-using

    • Good morning Amr,

      Sounds like you’re 90% there with the reals working but not the integers.

      Can you check to see if the Integer array you mapped is a 16 bit INT, and not a 32 bit DINT?

      PS – The process I used in this video for DH-485 would be nearly identical for DF1 and CompactLogix.

      Hope this helps,

      Shawn Tierney,
      Instructor at http://www.TheAutomationSchool.com

      Find my articles or comments helpful? Check out my courses here.