Update: For the latest procedure see our article HERE.
In today’s article we walk you through the steps to import a MicroLogix program into a Micro800 using the Connected Components Workbench (CCW) conversion tool.
Part One: Export your MicroLogix Program
Step 1) The first step is to open your MicroLogix 1000 program in RSLogix Micro (or 500) and preform a “Save As”
Step 2) In the “Save As” dialog box you’ll want to choose the type of “Library Files (*.SLC)” but don’t click on “Save” just yet…
Step 3) You’ll also want to select the “Export Database” box, and insure the “Export file type” is set to “Logix.” Once done, click on “Save”
Step 4) Now when the “Export SLC Format” window pops up, insure that “Complete Program Save” is selected along with all the “Export Options,” then click on “OK.”
Step 5) You should now see the “Export Results” window which should look like the below:
At this point you have exported your MicroLogix 1000 program and you’re ready to import it into CCW.
Part two: Import your MicroLogix program into CCW
NOTE: To complete the following steps you’ll need CCW v8 and the MicroLogix to Micro800 conversion tool which we discuss how to obtain in this article here.
Step 1) Open CCW, and under the “Tools” menu select “MicroLogix Library Conversion…”
Step 2) In the conversion window select your source project as the files you exported from RSLogix above. Then choose the model number of the Micro800 you would like to convert it to. When all selections have been made, click “OK”
Note: Despite the picture of the MicroLogix 1200, the tool clearly states it only works with MicroLogix 1000 files.
Step 3) After a few moments you should see your new Micro800 open with the imported code. You may also see a window with several warnings. At this point it’s recommended you review all the warnings, as well as compare the original file to the new one to insure everything imported correctly:
For more information on converting MicroLogix projects to the Micro800 using CCW, check out our previous articles on the subject below:
- Rockwell releases MicroLogix 1000 to Micro800 Migration Guide
- Rockwell releases Micrologix 1000 to Micro800 Conversion Tool
- How to get Rockwell’s Micrologix to Micro800 Conversion Tool
- MicroLogix 1000 and 1500 “end of life” date announced
- Micrologix 1000 Migration Options discussed
I hope the above article detailing how to import MicroLogix programs into Micro800s using the CCW conversion tool was helpful.
If you have any comments, questions, or suggestions, please feel free to leave them with us by submitting the “post a comment or question” link below.
Until next time, Peace ✌️
If you enjoy this episode please give it a Like, and consider Sharing as this is the best way for us to find new guests to come on the show.
Shawn M Tierney
Technology Enthusiast & Content Creator
Eliminate commercials and gain access to my weekly full length hands-on, news, and Q&A sessions by becoming a member at The Automation Blog or on YouTube. You'll also find all of my affordable PLC, HMI, and SCADA courses at TheAutomationSchool.com.
- Copia’s Ai Copilot Documents, Converts & Writes PLC Code (P228) - November 20, 2024
- Automation Q & A for November 15, 2024 (QA023) - November 15, 2024
- Siemens TIA Portal v20 (P227) - November 13, 2024
Discover more from The Automation Blog
Subscribe to get the latest posts sent to your email.