In today’s article I walk you through how to set or change a CompactLogix processor’s Ethernet address through its USB port using RSLinx Classic.
Step 1) Confirm your RSLinx RSWho window browses your CompactLogix via the USB driver
Open RSLinx and check to be sure your CompactLogix is showing up under the USB driver as shown below:
NOTE: If you would like to know how to setup an RSLinx driver to communicate to a CompactLogix processor using a USB connection, see our previous article HERE.
Step 2) Select the CompactLogix processor
The next step is to select the CompactLogix processor under the USB driver as shown below:
Step 3) Right click on the CompactLogix and select Module Configuration
Right click on the CompactLogix processor and select “Module Configuration” from the menu as shown below:
Step 4) Select the “Port Configuration” tab
In the popup window select the “Port Configuration” tab:
Step 5) Enter in a new Ethernet address and insure “Static” is selected
Now you can enter in an Ethernet address for your CompactLogix’s Ethernet port. Also be sure “Static” is selected, and then click on OK:
Step 6) Accept Configuration
The final step is to accept the configuration by clicking on “Yes,” after which your CompactLogix will have the Ethernet address you entered above:
NOTE: Watch me run through the above steps in today’s video episode of The Automation Minute!
I hope the above article on how to set or change a CompactLogix’s Ethernet address through its USB port using RSLinx was helpful.
If you have any questions or comments, please feel free to share them with us by clicking on the “post a comment or question” link below.
Until next time, Peace ✌️
If you enjoy this episode please give it a Like, and consider Sharing as this is the best way for us to find new guests to come on the show.
Shawn M Tierney
Technology Enthusiast & Content Creator
Eliminate commercials and gain access to my weekly full length hands-on, news, and Q&A sessions by becoming a member at The Automation Blog or on YouTube. You'll also find all of my affordable PLC, HMI, and SCADA courses at TheAutomationSchool.com.
- Copia’s Ai Copilot Documents, Converts & Writes PLC Code (P228) - November 20, 2024
- Automation Q & A for November 15, 2024 (QA023) - November 15, 2024
- Siemens TIA Portal v20 (P227) - November 13, 2024
Discover more from The Automation Blog
Subscribe to get the latest posts sent to your email.
Hi Shawn,
I am relatively new to EtherNet/IP PLCs. Right now the PLC is getting its IP address from a DHCP server, but I would like to change it to a fixed IP address. I followed your steps and upon selecting the “Port Configuration” tab I am getting the following message:
“Unable to read the module’s Port Configuration. The default values will be shown”
Could it be because I have already a project downloaded onto it? I am a bit lost now what I need to do?
Thanks and regards
Carmelo Curmi
Good morning Carmelo,
I’ll need some more info to help:
– What PLC and firmware are you using?
– Also, how old is your RSLinx?
– And what port are you going through to change its IP Address?
– Can you trying going through the other port to change the IP address?
Sincerely,
Shawn Tierney,
Instructor at TheAutomationSchool.com
Join my free community to follow along! You can also become a member and support our work at: Automation.Locals.com