Today you’ll find Ethernet in almost every manufacturing facility, and on most all modern automation systems. But many facilities also have an installed base of legacy PLC-5 systems, and often clients call asking how they can add Ethernet connectivity to their legacy PLC-5’s.
Before we answer that question, lets first review the communication options available on the PLC-5 processor.
The original processors (5/10, 5/12, 5/15, & 5/25) which were released beginning in 1985, came with two connectivity options built into every model:
- Data Highway Plus (DH+, also known as Peer Communication Interface or PCI)
- Remote I/O (RIO.)
The second generation of PLC-5 processors (5/11, 5/20, 5/30, 5/40, 5/60, 5/80,) known as the “New Platform” (NP) PLC-5, had an additional 25 pin RS-232 port, and could also be ordered with an optional Ethernet or ControlNet port.
So for all those PLC-5 processors without the built-in Ethernet port I list five options below which allow you to add Ethernet communications to your non-Ethernet PLC-5:
New Option: ANC-100e EtherNet/IP to DH+ Gateway
From ANC: “The ANC-100e is an economical and high performance, “pocket-sized” converter interfacing Factory Automation Devices between Ethernet/IP and Allen-Bradley Data Highway Plus DH+”
Pros:
Works with any DH+ device
Cons:
It’s not free?
PNs and Prices
ANC-100e EtherNet/IP to Allen Bradley DH+ Gateway $1,195.
Option 1: EtherNet/IP to Allen Bradley Remote I/O or DH+ Gateway (works with all DH+ devices)
From Prosoft: “The EtherNet/IP to Remote I/O or DH+ (AN-X2-AB-DHRIO) Gateway is designed to help customers initiate a phased migration approach to replacing or upgrading legacy Remote I/O, HMI’s or Drives. The AN-X2-AB-DHRIO gateway has multiple operating modes that are selected during initial configuration and are described below..”
Pros:
Works with any DH+ device
Cons:
It’s not free?
PNs and Prices
AN-X2-AB-DHRIO EtherNet/IP to Allen Bradley Remote I/O or DH+ Gateway $1,895.
Option 2: 1756 DH+ to Ethernet Gateway (works with all DH+ devices)
A very common option to bridge from Ethernet to DH+, CNET, and DNET, a 1756 chassis with an Ethernet module and a single DHRIO module provides for the bridging from Ethernet to two DH+ networks at 57.6K or 115K, or one DH+ at 230K.
Pros:
One Ethernet gateway to many networks
Direct access to PLC-5 Data Tables
No programming needed to bridge Ethernet to DH+
Add additional modules for additional networks: ControlNet, Devicenet, DH+, DH-485, or 3rd party modules from Prosoft
Cons:
Expensive solution for a single PLC
PNs and Prices
1756-A7: 7 SLOT CONTROLLOGIX CHASSIS $504.00 list price from A-B
1756-ENBT: CLX ETHERNET/IP BRIDGE $2150.00 list price from A-B
1756-PA75: 85-265V AC POWER SUPPLY $911.00 list price from A-B
1756-DHRIO: DH+/RIO BRIDGE $1,910.00 list price from A-B
(Obsolete) Option 3: DF1 to Ethernet/IP converter: (New Platform PLC-5 models only)
If your New Platform PLC-5’s serial port is available, you can easily add a DF1 to Ethernet/IP converter (1761-NET-ENI.)
Pro’s:
Least expensive option
Direct access to PLC-5 Data Table
Has built in email capability (converts PLC MSG to an email)
ENI configuration is done with a free utility
Con’s:
Only three simultaneous bi-directional connections to PLC-5 at any given time
The PLC-5 serial port is limited to 19.2K (low bandwidth)
Requires PLC-5 NP processor with available serial port
If you have an HMI on the serial port you can use the A-B Serial DF1 port splitter (1747-DPS1) but you’ll be splitting the bandwidth with the HMI.
PNs and Prices
1761-NET-ENI
$893.00 list price from A-B
1761-CBL-PM02
$74.10 list price from A-B
$25.00 from Amazon
9 Pin to 25 Pin adapter
$10 from Amazon
(Obsolete) Option 4: ENET Sidecar: (New Platform PLC-5 models only, firmware upgrade may be needed, )
If your New Platform PLC-5 has the correct firmware, or if you’re willing to purchase the firmware upgrade, and you have the ability to move whatever module you have in the first I/O slot (directly to the right of the processor,) the 1785-ENET Ethernet sidecar is an option you can consider.
Pros:
High Speed connection to PLC-5
Direct access to PLC-5 Data Table
Channel 3a configuration is simple
Cons:
Need to move and readdress I/O module in slot 1
Will likely need to update PLC-5 firmware chip which can be expensive
PNs and Prices
1785-ENET
$3720.00 list price from A-B
5/80 Firmware
~$685.00 from A-B (most expensive version, price circa 2005)
(Obsolete) Option 5: Prosoft Ethernet Module for 1771 Chassis and all PLC-5 Processors: (works will all PLC-5 models)
From Prosoft: “Support for the storage and transfer of up to 4000 registers to/from the PLC processor using the block transfer. The module can send read or write commands to remote devices on the Ethernet/IP network. The MVI71-DFNT also has 20 servers that allows the module to receive commands from remote devices. The MVI71-DFNT Pass-Through server allows the user to edit, download, and upload the PLC ladder logic using an Ethernet connection. Up to 100 commands can be configured by the user.”
Pros:
Works with any PLC-5 in any SLOT
Cons:
Requires programming (Prosoft tech support historically has been good)
– Block Transfers needed in PLC-5 Program
PNs and Prices
MVI71-DFNT EhterNet /IP Communication Module ~$2,159 (circa 2005)
I hope you’ve found this article about how to add Ethernet to non-Ethernet versions of the Allen-Bradley PLC-5 helpful. If you have a question or would like to offer your own option please click on the “post a comment or question” link below to comment on this article.
Until next time, Peace ✌️
If you enjoy this episode please give it a Like, and consider Sharing as this is the best way for us to find new guests to come on the show.
Shawn M Tierney
Technology Enthusiast & Content Creator
Eliminate commercials and gain access to my weekly full length hands-on, news, and Q&A sessions by becoming a member at The Automation Blog or on YouTube. You'll also find all of my affordable PLC, HMI, and SCADA courses at TheAutomationSchool.com.
- First Look: New Rockwell Products Shown At Automation Fair 2024 (TME06) - December 6, 2024
- Automation Q & A for December 6, 2024 (QW025) - December 6, 2024
- Programming Options for CompactLogix and ControlLogix (2024) (M5E43) - December 5, 2024
Discover more from The Automation Blog
Subscribe to get the latest posts sent to your email.
Thank you Shawn for your post that helped me to see the different solutions to connect old PLC5 to Ethernet. .
Regarding the connection from PLC5 to 1761-NET-ENI, the proposed 1761-CBL-PM02 cable will not fit because the cable has a 9 Pin SubD connector and the PLC5 has a 25 Pin SubD connector. An adapter is required I think.
Alan
Good evening Alan,
Thanks for your comment. Yes, you are correct about the PM02 which is why I also listed the 9-25 pin converter under it – sorry it wasn’t more obvious.
Have a great evening,
Shawn Tierney
Join my free community to follow along! You can also become a member and support our work at: Automation.Locals.com
[…] How to add Ethernet communications to a non-Ethernet PLC-5 […]
[…] NOTE: The newest version of this article is located HERE […]