The MicroLogix 1400 is one of the few Allen-Bradley PLC’s with a small LCD display and navigation keys on the front of the unit, and these can be used to find the PLC’s MAC and IP address.
Displayed once?
This built-in LCD display is actually quite functional, allowing users to access a lot of information about the PLC. However, in what could only be an effort to minimize cost, information that can be found on the display typically can’t be found elsewhere on the unit. For instance, since the I/O status is displayed on the built in LCD, the PLC contains no I/O status LEDs. And because the MAC address can also be found using the built-in display, its not listed on the product label like other Allen-Bradley Ethernet devices.
However, the built in LCD Display and navigation keys are easy to use, and below I list the steps to take to display the MAC and IP address:
To view the MicroLogix 1400 MAC and IP address from the front of the MicroLogix 1400
To access the menu, start by pressing the ESC key to get the main menu of “I/O Status, Monitoring, Mode Switch”
Press the arrow down key four times to select “Advanced Set” and press the OK key
Press the arrow down key two times to select “ENET Cfg” and press the OK key
Press the OK key again with “Status” selected:
You will now see the MicroLogix MAC address and IP address displayed
To return the MicroLogix 1400 to the main menu press the ESC key until you see “I/O Status, Monitoring, Mode Switch”
To change the MicroLogix 1400 IP address from the front of the MicroLogix 1400
Press the ESC key until you see the main menu of “I/O Status, Monitoring, Mode Switch”
Press the arrow down key four times to select “Advanced Set” and press the OK key
Press the arrow down key two times to select “ENET Cfg” and press the OK key
Press the arrow down key once to select “IP Address” and press the OK Key
At this point if a password has been added you will need to enter it here. Or if no password exists you can just press the OK key
On the next screen you will see the setting for BootP, DHCP, or Static ENET Mode. In most cases “static” will be chosen to allow the MicroLogix 1400 to maintain a single IP address. Press the OK key to continue
On this screen you will now see the IP address which you can modify to your desired setting. Press OK when done to set the Subnet Mask and Default Gateway settings
When done, press the ESC key until you see “I/O Status, Monitoring, Mode Switch”
How to view the MicroLogix 1400 MAC and IP address inside the RSLogix offline file
If you don’t have access to the MicroLogix 1400, but do have the RSLogix file uploaded from the PLC, you can also still the MAC and IP address.
First, open the file in RSLogix
Next, open the Channel Configuration and select Channel 1. As seen below, this will display the MAC and IP address of the unit the file was uploaded from:
I hope you’ve found the above steps to finding the MicroLogix 1400’s MAC and IP address helpful. If you have any comments or questions please don’t hesitate to post a comment or question by using the “post a comment or question” link below.
Until next time, Peace ✌️
If you enjoy this episode please give it a Like, and consider Sharing as this is the best way for us to find new guests to come on the show.
Shawn M Tierney
Technology Enthusiast & Content Creator
Eliminate commercials and gain access to my weekly full length hands-on, news, and Q&A sessions by becoming a member at The Automation Blog or on YouTube. You'll also find all of my affordable PLC, HMI, and SCADA courses at TheAutomationSchool.com.
- What’s New at Insights: Member Coupons, New Podcast, New Courses and more! (W015) - December 16, 2024
- Anybus Defender Industrial Security Devices (P231) - December 11, 2024
- First Look: New Rockwell Products Shown At Automation Fair 2024 (TME06) - December 6, 2024
Discover more from The Automation Blog
Subscribe to get the latest posts sent to your email.
[…] NOTE: The newest version of this article is located at our sister site, The Automation Blog […]