The MicroLogix 1100’s LCD display allows access to many of it’s features and functions.
In today’s article, we show you how to use it to enable default comms:
NOTE: When “Default Comms” is enabled, the MicroLogix 1100’s Channel 0 serial port is toggled back to the factory default settings. These settings include the DF1 Full Duplex protocol, a baud rate of 19.2K, and CRC error checking. When “Default Comms” is disabled, Channel 0 returns to the currently loaded program’s settings.
Enabling Default Comms on the MicroLogix 1100
1) When the MicroLogix 1100 is powered on, it displays the I/O Status screen as shown below:
2) To enable “Default Comms,” we need to access the LCD menu. To do this, press the ESC button and you should see the display below:
3) Next, press the down arrow button four times to select “Advanced Set,” then press the OK button:
4) Here, press the down arrow button once to select “DCOMM CFG,” then press the OK button:
5) Now press the up arrow button once to select “Enable,” and press the OK button.
6) You should now see the message, “Comms config set to DF1 default.” You should also see the DCOMM indicator displayed near the top left of the LCD.
7) To return to the I/O Status display, press the ESC button until you see the main menu, and then select “I/O Status” and press the OK button:
I hope the above procedure on how to use the MicroLogix 1100’s LCD display to enable “Default Comms” was helpful.
If you have any comments, questions, suggestions, or corrections, please feel free to leave them with us by filling out the “post a comment or question” link below.
Until next time, Peace ✌️
If you enjoy this episode please give it a Like, and consider Sharing as this is the best way for us to find new guests to come on the show.
Shawn M Tierney
Technology Enthusiast & Content Creator
Eliminate commercials and gain access to my weekly full length hands-on, news, and Q&A sessions by becoming a member at The Automation Blog or on YouTube. You'll also find all of my affordable PLC, HMI, and SCADA courses at TheAutomationSchool.com.
- SLC-500 Migrations Compared: SoftPLC vs Studio 5000 (S2E10) - November 21, 2024
- Copia’s Ai Copilot Documents, Converts & Writes PLC Code (P228) - November 20, 2024
- Automation Q & A for November 15, 2024 (QA023) - November 15, 2024
Discover more from The Automation Blog
Subscribe to get the latest posts sent to your email.