Earlier in the week in this blog post we discussed how flashing a PanelView Plus 6 over the network could take hours.
Today we’ll take you step-by-step through a quicker way of flashing your PVPlus 6 by doing so using a memory card.
Flashing your PanelView Plus 6 firmware using a memory card or USB flash drive:
Step 1:
Launch the “ME Firmware Upgrade Wizard found under All Programs, Rockwell Software, FactoryTalk View, Tools:
Step 2:
Choose “create firmware upgrade card,” then choose your detonation folder (typically the drive letter of your memory card or flash drive,) and then choose the model of your PanelView Plus:
Step 3:
Now choose the version you wish to upgrade your PanelView Plus to:
NOTE:
To obtain PanelView Plus firmware, visit the below Rockwell webpage and search on PanelView Plus (no contract required.)
Step 4:
Select any third party PLC Kepware drivers:
Step 5:
If everything looks right on the summary page, press finish and the wizard will copy the correct files to your memory card:
Step 6:
The Firmware should be copied to your card, after which you’ll be prompted to click on OK:
NOTE:
Before proceeding with the PVPlus firmware upgrade, back up all your .MER files which are currently on the terminal. See this blog post for more information on how to do this.
Step 7:
Insert the memory card (or usb flash drive) into the PanelView Plus terminal and select “Upgrade” from the popup window. After roughly five minutes your PanelView Plus firmware upgrade will be complete and you can now remove your upgrade memory card.
I hope the above step-by-step instructions on how you upgrade your PanelView Plus firmware using a memory card was helpful.
If it was and you’ll like to thank us please take a moment and visit our Support page for ideas on how you can support our site.
Until next time, Peace ✌️
If you enjoy this episode please give it a Like, and consider Sharing as this is the best way for us to find new guests to come on the show.
Shawn M Tierney
Technology Enthusiast & Content Creator
Eliminate commercials and gain access to my weekly full length hands-on, news, and Q&A sessions by becoming a member at The Automation Blog or on YouTube. You'll also find all of my affordable PLC, HMI, and SCADA courses at TheAutomationSchool.com.
- What’s New at Insights: Member Coupons, New Podcast, New Courses and more! (W015) - December 16, 2024
- Anybus Defender Industrial Security Devices (P231) - December 11, 2024
- First Look: New Rockwell Products Shown At Automation Fair 2024 (TME06) - December 6, 2024
Discover more from The Automation Blog
Subscribe to get the latest posts sent to your email.
Is it feasible to downgrade a firmware version on a PanelView Plus? I currently have an Mer file running on the 6.1, but I want to replace the logic module since it has a flaky communication ethernet port causing communication errors. The module that I have currently in inventory has a 7.0.55.13 firmware revision. What is your recommendation on this?
Good afternoon Cesar,
Yes, as long as the terminal has the old firmware firmware available.
For instance, I recently downgraded my 5.1 panel to 3.1 using the firmware available for my model on ab.com.
For a PVPlus 6, I would imagine you could take it all the way back to 6.0, but again check to see which firmware is available for your exact model at ab.com.
Hope this helps,
Shawn Tierney
Join my free community to follow along! You can also become a member and support our work at: Automation.Locals.com
Firmware crazy