Why won’t RSLinx Enterprise show up in Emulate 5000?

SoftLogix 5800 with Processor but No RSLinx EnterpriseLast week a client sent me a CompactLogix file and PanelView Plus file to review.

To test these files together I usually change the CompactLogix file into an Emulator file in RSLogix 5000, and then download it to Emulate 5000 (a processor emulator for RSLogix 5000.)

Once this is done, I open the PanelView Plus project in ViewStudio and modify the RSLinx Enterprise (RSLE) shortcut to point at the emulator. However, in this case when I proceeded to update my RSLE shortcut, browsing the virtual backplane didn’t display my emulated processor?

RSLinx Enterprise does not find SoftLogix processorSo, I first restarted the RSLE service, and when that didn’t work I restarted my virtual PC. With it still not working, I headed of to the Rockwell Knowledgebase and the only helpful advice it had was to reinstall RSLinx Enterprise. After a painfully long re-install of RSLE, I was indeed able to browse to my emulated processor, update my shortcut, and test the ViewStudio project.

Once that issue was resolved, I ran into a second issue. As I was emulating a CompactLogix file, and those processors are located in slot 0, I attempted to put my virtual processor in slot 0 of the virtual backplane, However, when I right clicked on slot 0 the only versions available were v17 – v20, but my client’s file was version 16.

SoftLogix 5800 add processor to slot 0I was a little confused as I was running Emulate 5000 v20, which on Windows XP should had provided support for version 12 to 20. After confirming this fact in the product’s release notes, I tried another slots and was able to chose from versions 12-20. I didn’t research this further, but thought it was worth passing on since I hadn’t noticed this slot / version restriction before.

SoftLogix 5800 add processor to slot 1I hope the above information about why RSLE might not show up in Emulate 5000 is helpful.

If you have a question or comment please don’t hesitate to share them with us by clicking on the “post a comment or question” link below.

Until next time, Peace ✌️ 

Shawn M Tierney
Technology Enthusiast & Content Creator

Have a question? Join my community of automation professionals and take part in the discussion! You'll also find my PLC, HMI, and SCADA courses at TheAutomationSchool.com.

If you found this content helpful, consider buying me a coffee here.

Shawn Tierney

(4,268 views)

5 COMMENTS

    • I figured this out. I was unable to move it via RSLinx driver config (kept saying it was in use). I found a registry key (HKLMSOFTWAREWow6432NodeRockwell SoftwareRSLinxDriversAB_VBPAB_VBP-1), modified the “Slot” key to “0x0000000F”, and now RSLinx resides in slot 15.

      • Good morning Heath,

        Thanks for the tip!

        I don’t currently have Softlogix installed, but I believe you can also right click on RSLinx Classic to change its slot number from right inside the chassis monitor?

        For RSLinx Enterprise I know you have to change its slot number from within View Studio or the Ft Admin Console by editing the VBP there.

        Sincerely,

        Shawn Tierney